• 200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
  • 200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
  • 200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
  • 200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
  • 200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
  • 200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer

200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer

Certification: CCC, ISO90001
Application: Electronic, Industrial, Rmu/Gis/Transformer
Product Name: Loadbreak Elbow Connector
Material: EPDM
MOQ: 3PCS
Rated Current: 200A
Samples:
US$ 15/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Manufacturer/Factory & Trading Company
Gold Member Since 2023

Suppliers with verified business licenses

Guangdong, China
to see all verified strength labels (23)
  • Overview
  • Product Description
  • Packaging & Shipping
  • Company Profile
  • FAQ
Overview

Basic Info.

Model NO.
NRZT-15/200
Rated Voltage
15kv
Cable Section
Cable 25~150mm2
Function
Connection
Certificate
IEEE 386
Keywords
High Quality
Usage
Electrical Equipment
OEM/ODM
Accept
Transport Package
Carton + Wooden Case
Specification
28*23*21
Trademark
Nan Rui Electric
Origin
China
HS Code
8538900000
Production Capacity
3000PCS/Month

Product Description

Product Description

15kV/200A Elbow Connector

1.The 15kV/200A Elbow connector suitable for master or branch distribution of power system of padmound
transformer,ring main unit and cable branch box. 2.It can mate with 200A bushing insert and 200A jack ofT- II connector. 3.Conductor cross section is 25~ 120mm²
 

Executive standard:

★ IEEE std386-2006 Separable insulated connector system for power distribution systems above 600V;
★Exposed semiconductor sheath of ANSI IEEE592-1990 high voltage cable joints and separable insulated connectors;
★IEC60502 rated voltage 1kV (Um=1.2kV) above to 30kV (Um=36kV) extruded insulated power cable and its accessories;
★IEC61442 rated voltage 6kV (Um=72kV) to 30kV (Um=36kV) power cable accessories test method;
★GB12706-2002 rated voltage 1kV (Um=12kV) to 35kV (Um=405kV) extruded insulated power cables and accessories;
★GB311.1-1997 Insulation coordination of high-voltage power transmission and distribution equipment;
★GB/T41.9-1999 technical conditions for high-voltage bushings;
★GB11032-2010 AC gapless metal oxide arrester;
★ DIN47636-7-1990 Power cable with protruding cone can be divided into accessories set, Um below 36kV bushing and 
can be divided into the connecting piece device ruler.

200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer

Electrical Performance
No.
Content / Item
Unit
Value
1
Rated voltage
kV
8.7/14.4
2
Rated current
A
200
3
Partial discharge test
≤pC(kV)
42
4
AC voltage test
kV/5min
≤10pC(13.5kV)
5
DC 15 Miunte Withstand
kV
53
6
BIL and Full Wave Crest
KV
95
7
Minimum Corona Voltage Level
kV
13.5

Cable Selection
tapy
Product bore size
( φ mm)
Conductor cross-sectional area
(mm²)
Conductor diameter
( φ mm)
Cable Insulation Diameter
( φ mm)
A
15.8
35~50
5.9~8.5
16.0~20.0
B
18.8
70~95
9.8~11.7
20.1~23.0
C
21.8
120~150
12.8~14.7
23.1~26.0

 

 
Packaging & Shipping
200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
Company Profile
 
 
200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer



Shenzhen Nanrui Electric Technology Co., Ltd. has specialised in the design and development of foreign high voltage cable accessories for nearly 20 years.
The company has moulds, hardware design and processing of hardware workshop, and a collection of rubber
products composite moulding and product performance testing in one of the rubber workshop. We have achieved
100% inspection of the products. The company also has ISO9001:2015 certification, with scientific management mode and strict production standards.
200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer

200A 15kv Loadbreak Elbow IEEE 386 Cable Accessories 8.7/14.4kv Load Break Elbow for Transformer
FAQ

Q1. What is your lead time?
A1: Stock: 3-5 days in general. No stock: 15-30 days after samples confirmed. Or please contact us by email for specific lead time base on your order quantities.
Q2. How does your factory do regarding quality control?
A2: Quality is priority. We always attach great importance to quality control from the very beginning to the end: 1) All raw material we used are non-toxic, environmental-friendly; 2) Skillful workers pay great attention to each details in handling the producing and packing processes; 3) We have a professional QA/QC team to ensure the quality.
Q3. Do you accept OEM or ODM order?
A3: Yes, we accept both OEM and ODM for customers.
Q4. What are your terms of delivery?
A4: We can accept EXW, FOB, CIF, etc. You can choose one which is the most convenient for you.
Q5. What is the payment way?
A5: TT, Pay Later, West Union,Online Bank Payment. Should you have other questions, please let us know. We'll add answers here for your further references. Thank you.

 